Greencisco Industrial Co., Ltd.
UPS with multi outputs: -48Vdc/220Vac
UPS output voltage:-48Vdc and 220Vac

Application
Applied to Ethernet,Servers,Exchangers,computers,Local area network (LAN) and metropolitan area network,Indoor wireless network,Telecommunications equipment,48V distributed system,Indoor distribution and extension system,Mobile base stations,WLAN,Satellite communication,microwave station

Introduction

Modular online UPS consists of the distribution frame, monitoring module and rectifier module and inverter module. Output voltage can be with -48VDC, 220VAC output.

UPS with smart internal battery charger and battery management system for lithium battery, lead acid battery, NiCd battery and LiFePO4 battery, ect.
With high technology such as soft switching, intelligent fan cooling, and Magnetic Shield in the design and development of the power supplies. Power system are also of high efficient and high reliability, with extra low electromagnetic interference, which make them easy to maintenance.
This state-of-the-art solution is especially designed for eliminating the power loss, extra high or low voltage of utility power, voltage sags or damped oscillation, high-voltage pulse, voltage fluctuation, surge voltage, harmonic distortion, clutter immunity, and frequency fluctuation etc., delivering safe and reliable power supply guarantee for users load.
Which can be widely applied to the Base Station of GSM/CDMA, Exchange Bureau of medium-low capacity, Satellite Communication, Data Communication, mobile communication, Access network, microwave communication, electric power system, ect.
Features
● Input:90-280VAC,output:-48Vdc or 220Vac
● Input:48Vdc,output: 220Vac,with RS232,RS485 communication ports 
● Adoption of active power factor compensation technology with factor >0.99
● Wide operating range of AC input voltage: 90~280VAC
● Operating temperature range: -25℃~+55℃
● Zero current/voltage switching tech with high efficiency ≥91%
● Perfect battery management system
● Hot-swappable

Specification

Model
HP9001 modular online ups
Parameter Minimum Normal Maximum Unit Remark
Input voltage range 90 220 280 Vac working voltage range:100-240vac
Input frequency 45 50 65 Hz
Input impact current 50 A cold start at 280Vac input
Power factor 0.99 220Vac
DC input voltage 40 48 58 Vdc
DC current 65 A
Output Dc voltage -43.2 -53.5 -58 Vdc
Output current 0 60 A 176-285Vac
Output current 0 30 A 90-176Vac
Efficiency 90 92 % 220Vac
Efficiency 83 85 % 110Vac
Ripple(Vp-p) 200 mV
Load regulation ±1 %
Voltage regulation ±1 %
Stabilized voltage precision ±1 %
AC output voltage 220 Vac
AC output current 7.7 A
Power factor 0.8
Frequency 50Hz
Stabilized voltage precision ±5 %
Capacity 2000 VA
1600 W
Waveform pure sine wave
THD <3%
Insulation Requirement
Input-output 3000Vdc/10mA/1min
Input-chassis 1500Vdc/10mA/1min
Output-chassis 500Vdc/10mA/1min
Leakage current <3.5mA
Input-output 2000VAc/10mA/1min
Input-chassis 500Vdc/10mA/1min
Output-chassis 1500Vac/10mA/1min
Resistance Humidity:90%,testing voltage:500Vdc,input-output/input-ground/output-ground not be less than 10MΩ
Normal Temperature -15 25 +55 °C startup at -40°C,when temperature at 65°C,output derating to 80%
Operating temperature -25 +55 °C
Storage temp -40 +80 °C
Humidity 5 90 % no condensing
Atmospheric press 70 106 Kpa
Altitude 0 3000 m
Cooling Forced fan
Ingress protection machine can work at dust of 5um,density<3*104/m3
Size 600x415x685mm
Weight 48kgs
EMC standard
Harmonic current IEC61000-3-2[6] Class A
RS IEC61000-4-3 Level 3
CS IEC61000-4-6 Level 3
ESD EN/IEC 61000-4-2,contact discharge+/-6kv,Air discharge:+/-8kv,Conductor contact discharge:+/-2kv
RE EN55022 Class B
CE Input:EN55022 Class B
EFT/B IEC61000-4-4 Level 3
Surge IEC61000-4-5 Level 4
Lightning AC input bare ±5 times of impacts of 5KA, lightning strike impact current waveform of 8/20us with interval of 1 minute
DIP(220Vac) EN/IEC61000-4-11
Safety standard IEC60950-1,UL60950-1,CAN/CAS-C22.2, No. 60950-1,EN60950-1
Hot plug Yes
Reliablity <250000 hours
Parallel N+1 redundancy and current sharing available at parallel operation
Environment protection No cadmium,hydride or fluoride,No organic compounds,no asbestos,packages are recyclable
About Us
Company Introduction
Principles
Mission
Global Certification
Contact us
Solution
New Energy
Network Solutions
Industrial Solutions
Household Solutions
Motive Power Solutions
Products
UPS
Rectifier and charger
Batteries
Photovoltaic Energy
Inverter and Stabilizer
Support
Partners
Technical Support